Shizuki Low voltage line series reactor

Shizuki Low voltage line series reactor

Shizuki Low voltage line series reactor Solve your harmonic problems with Shizuki series reactors   APPLICABLE STANDARD The reactors are designed, manufactured and tested to meet the requirements of the latest standard IEC 60289-1988, JIS C 4901-...
Call Seller for Quote
Model: -
Company Information
Name : Piohm Corporation Co.,Ltd.
Contact : พายโอห์ม คอร์ปอเรชั่น
Tel : Please login.

Shizuki Low voltage line series reactor
Solve your harmonic problems with Shizuki series reactors

 

APPLICABLE STANDARD
The reactors are designed, manufactured and
tested to meet the requirements of the latest
standard IEC 60289-1988, JIS C 4901-2000.

 

OPERATING CONDITIONS
1. Installation : Indoor use
2. Ambient temperature : -20ºC ~ +50ºC
3. Relative humidity : Not more than 85%
4. Altitude : Not exceeding 2,000 meters above
 sea level 

 

ELECTRICAL CHARACTERISTICS
1. Output tolerance : -5% to +10%
2. Withstand voltage test : Between terminals connected together and  core and between terminals. 3k volts, 1 minute.
3. Maximum permissible current : Maximum permissible current shall be  110% of the rated current. If the 5 th harmonic is contained, it is defined as a rms value of the resultant current with the 5th harmonic current not exceeding 10% of the fundamental current.
4. Maximum permissible momentary current : Maximum permissible  momentary current shall be 25 times the rated current for 2 seconds Reactors shall not have thermal or mechanical damages when  subjected to the above current.
5. Temperature rise : The temperature of the winding, when it has  reached a constant value after 155% of the rated current is applied continually at the rated frequency. Shall not exceed 85ºC.
6. Thermal sensor : Temp. setting 125ºC, Contact Normally Close, 125VAC 8.0Amp.